Installing the S7-400
2-14
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Step 4: Mounting Additional Racks
If you assemble an S7-400 with two or more racks, you must allow additional
clearance between the individual racks or install a fan subassembly or cable duct.
The figure below shows the clearance you must allow between two racks of the
S7-400 during installation.
110 mm
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18