B-4
C7-613 Control System
A5E00138934-03
Error Code
(W#16#...)
Remedy
Cause
8223
The DB for backing up the event
buffer on the MMC that is
specified in the “EVENT_DB”
parameter does not have the
“unlinked” attribute.
This check is performed only
after a backup job is initiated.
Check to determine whether the
“unlinked” attribute has been selected for
the specified DB. To select the “unlinked”
attribute, refer to the STEP 7 Online
Help.
8224
The DB for backing up the event
buffer on the MMC that is
specified in the “EVENT_DB”
parameter is write-protected.
This check is performed only
after a backup job is initiated.
Remove the write protection from the
specified DB. For information on
removing the write protection, please
refer to the STEP 7 Online Help.
8400
The language selection
“SetLang” specified in the
configuration DB (“CONFIG”) has
the value “0”.
Use the configuration interface to set the
language with which the C7-613 boots
up after restarting.
840 x
The language selection “SetLang
= x” specified in the configuration
DB (“CONFIG”) is not available.
Use the configuration interface to set the
language with which the C7-613 boots
up after restarting.
8406
The language selection
“SetLang” specified in the
configuration DB (“CONFIG”) has
a value > 5.
Use the configuration interface to set the
language with which the C7-613 boots
up after restarting.
84xy
Parameter assignment is faulty in
DB y of language x.
The values x and y mean:
•
x = Language index (1 to 5)
•
y = DB of the language (0 up to a
maximum of 5).
– 0 = Configuration DB
(“CONFIG”)
– 1 = First DB for process screens
(”SCREEN”)
The byte address within the DB at which
the error occurred is specified in the
parameter “ADDINFO” (hexadecimal
form).
Information on the DB structure is
contained in Appendix C.1 to C.5.
The parameter assignment is described
in Section 4.3.
Summary of Contents for SIMATIC C7-613
Page 14: ...Contents xiv C7 613 Control System A5E00138934 03 ...
Page 56: ...Special Features of the C7 613 3 10 C7 613 Control System A5E00138934 03 ...
Page 90: ...Integration into the User Program 4 34 C7 613 Control System A5E00138934 03 ...
Page 134: ...Maintenance 6 4 C7 613 Control System A5E00138934 03 ...
Page 160: ...A 26 C7 613 Control System A5E00138934 03 ...
Page 176: ...B 16 C7 613 Control System A5E00138934 03 ...
Page 192: ...C 16 C7 613 Control System A5E00138934 03 ...
Page 198: ...Index Index 6 C7 613 Control System A5E00138934 03 ...