B-12
C7-613 Control System
A5E00138934-03
System Message
Remedy
Cause
$ 003
The event buffer is empty.
There are no messages in
the event buffer.
–
$ 004
Parameter assignment
error
There is an error in a data
block with configuration
data.
Eliminate the parameter assignment error. You
can obtain more detailed information in the
“RETVAL” error information and the “ADDINFO”
status information of the “HMI API” FB.
Reinitiate a parameter assignment for the
integrated HMI module. Since a valid parameter
assignment does not yet exist, a STOP to RUN
transition is sufficient.
$ 006
Parameters have not
been assigned to the
object.
The selected object is not
available, or there is no
configuration for the
requested object.
Configure the object (screen or info text).
$ 008
CPU is in STOP mode
Serves as a note, since
HMI functions are not
possible when the CPU is
in STOP mode.
Switch the CPU to RUN mode to perform the
HMI functions.
$ 009
No active faults.
The message is displayed
after selection of the
message level, if there are
no current operation/fault
messages.
–
$ 010
Backup of the event buffer
is under way.
The event buffer is being
transferred to the
EVENT_BUFFER on the
MMC. The message is
displayed until the backup
operation is completed.
Wait until the transfer operation is completed.
$ 011
Screen #0 is missing.
A process screen with the
number 0 has not been
created.
Check your configuration. Create the process
screen by using the configuration interface
.
Use
a general reset operation or select the special
screen “Reload application” to reinitiate a
parameter assignment for the integrated HMI
module.
$ 012
Unknown password
The entered password is
unknown.
Check your password. You may have entered
an incorrect figure. Reenter the password level.
$ 013
Inadmissible password
The entered password is
already in use.
Use another password.
Inadmissible password
The password does not
contain at least three
characters.
Use a password that has at least 3 characters.
$ 014
Illegal password level
The specified password
level does not match the
password or is too high.
Check your present password level. You may
have entered an incorrect figure. Reenter the
password level. Permissible password level lies
in the range of 0 to 3.
$ 015
Entry > upper limit value
The input value is greater
than the upper limit value.
The original value is
retained.
Repeat the entry with a lower value.
Summary of Contents for SIMATIC C7-613
Page 14: ...Contents xiv C7 613 Control System A5E00138934 03 ...
Page 56: ...Special Features of the C7 613 3 10 C7 613 Control System A5E00138934 03 ...
Page 90: ...Integration into the User Program 4 34 C7 613 Control System A5E00138934 03 ...
Page 134: ...Maintenance 6 4 C7 613 Control System A5E00138934 03 ...
Page 160: ...A 26 C7 613 Control System A5E00138934 03 ...
Page 176: ...B 16 C7 613 Control System A5E00138934 03 ...
Page 192: ...C 16 C7 613 Control System A5E00138934 03 ...
Page 198: ...Index Index 6 C7 613 Control System A5E00138934 03 ...