Configuration DBs
C-7
C7-613 Control System
A5E00138934-03
Table C-3 Structure of DB for Process Screens, continued
Address
Description
Type
Name
148
SCREEN[0].PIC_VAR[1].ACCESS
CHAR
Data type
“X”=BOOL
“C”=CHAR
“B”=BYTE
“I”=INT
“L”=DINT
“W”=WORD
“D”=DWORD
149
SCREEN[0].PIC_VAR[1].BITNO
BYTE
Bit number
0 to 7; must be 0 for all data types
except “X”.
150
SCREEN[0].PIC_VAR[1].UPPERLIM
DINT
Upper limit
If limit monitoring is switched on, the
variable is monitored at the input for
values > the upper limit. If the limit is
exceeded, a corresponding system
message is output.
154
SCREEN[0].PIC_VAR[1].LOWERLIM
DINT
Lower Limit
If limit monitoring is switched on, the
variable is monitored at the input for
values < the lower limit. If the lower
limit is exceeded, a corresponding
system message is output.
158 to
175
SCREEN[0].PIC_VAR[2].
Description for Variable 2
176 to
193
SCREEN[0].PIC_VAR[3].
Description for Variable 3
194 to
211
SCREEN[0].PIC_VAR[4].
Description for Variable 4
212 to
229
SCREEN[0].PIC_VAR[5].
Description for Variable 5
230 to
247
SCREEN[0].PIC_VAR[6].
Description for Variable 6
248 to
265
SCREEN[0].PIC_VAR[7].
Description for Variable 7
266 to
283
SCREEN[0].PIC_VAR[8].
Description for Variable 8
284 to
535
SCREEN[1]...
Screen description for Screen 1
to
15908 to
16159
SCREEN[63]...
Screen description for Screen 63
Summary of Contents for SIMATIC C7-613
Page 14: ...Contents xiv C7 613 Control System A5E00138934 03 ...
Page 56: ...Special Features of the C7 613 3 10 C7 613 Control System A5E00138934 03 ...
Page 90: ...Integration into the User Program 4 34 C7 613 Control System A5E00138934 03 ...
Page 134: ...Maintenance 6 4 C7 613 Control System A5E00138934 03 ...
Page 160: ...A 26 C7 613 Control System A5E00138934 03 ...
Page 176: ...B 16 C7 613 Control System A5E00138934 03 ...
Page 192: ...C 16 C7 613 Control System A5E00138934 03 ...
Page 198: ...Index Index 6 C7 613 Control System A5E00138934 03 ...