Technical data
A-3
C7-613 Control System
A5E00138934-03
Mechanical environmental conditions
Vibration
Tested in accordance with IEC 60068-2-6
•
Operation
10 Hz to 58 Hz, amplitude 0.075
58 Hz to 150 Hz, acceleration 9.8 m/s
2
•
Storage/transport in
packaging
5 Hz to 9 Hz, amplitude 3.5 mm
9 Hz to 500 Hz, acceleration 9.8 m/s
2
Shock test
•
Operation
•
Storage/transport in
packaging
Tested in accordance with IEC 60068-2-29
Half-sine: 150 m/s
2
(15 g), 11 ms, 18 shocks
250 m/s
2
(25 g), 6 ms, 1000 shocks
Fireproofing:
•
Terminal strips
•
Master strips in housing
FV2 (tested in accordance with IEC 60707)
FV0