A-14
C7-613 Control System
A5E00138934-03
Status, interrupts, diagnostics
Interrupts
•
No interrupts when operated as standard I/O
•
When using the technological functions,
cf.
S7-300 Programmable Controller, CPU31xC
Technological Functions” manual
Diagnostic functions
•
No diagnostics when operated as standard I/O
•
When using the technological functions,
cf.
S7-300 Programmable Controller, CPU31xC
Technological Functions” manual
Data for selecting an actuator for standard DOs
Output voltage
•
For signal “1”
Min. L+ (–0.8 V)
Output current
•
For signal “1”
– Rated value
0.5 A
– Permissible range
5 mA to 0.6 A
•
For “0” signal (residual current)
Max. 0.5 mA
Load impedance range
48
Ω
to 4 k
Ω
Lamp load
Max. 5 W
Parallel connection of 2 outputs
•
for redundant load control
Possible
•
For performance increase
Not possible
Digital input control
Possible
Switching frequency
•
For resistive load
Maximum 100 Hz
•
with inductive load to IEC 947-5, DC13
Max. 0.5 Hz
•
with lamp load
Maximum 100 Hz
•
Fast outputs with resistive load
Maximum 2.5 kHz
Inductive breaking voltage limited internally
to
(L+) – 48 V, typically
Short-circuit protected output
Yes, electronic
•
Response threshold
1 A, typically
Summary of Contents for SIMATIC C7-613
Page 14: ...Contents xiv C7 613 Control System A5E00138934 03 ...
Page 56: ...Special Features of the C7 613 3 10 C7 613 Control System A5E00138934 03 ...
Page 90: ...Integration into the User Program 4 34 C7 613 Control System A5E00138934 03 ...
Page 134: ...Maintenance 6 4 C7 613 Control System A5E00138934 03 ...
Page 160: ...A 26 C7 613 Control System A5E00138934 03 ...
Page 176: ...B 16 C7 613 Control System A5E00138934 03 ...
Page 192: ...C 16 C7 613 Control System A5E00138934 03 ...
Page 198: ...Index Index 6 C7 613 Control System A5E00138934 03 ...