Special Features of the C7-613
3-5
C7-613 Control System
A5E00138934-03
3.2
Status and Error Displays of the C7-613
Meaning of the status and error displays
The status and error displays are explained in the sequence in which they are
arranged on the C7-613.
Display
Description
Description
SF (red)
C7-613 group error
Is lit
when there are
•
hardware errors
•
firmware errors
•
Programming errors
•
Parameter assignment errors
•
Computing errors
•
Time-out
•
I/O errors during internal I/O functions
For exact error determination, a programming device/PC has to be
used and the diagnostic buffer has to be read out.
5 V DC
(green)
5 V DC supply for
the C7-613
Is lit
if the internal 5 V DC supply is okay.
FRCE (yellow) Reserved
Is lit
when a force request is active on the CPU.
RUN (green)
RUN mode of the
C7-613
Illuminates
when the C7-613 is executing the user program.
Flashes
(2 Hz) during the C7-613 startup (in addition, the STOP
display illuminates; after the STOP display goes out, the outputs
are enabled).
STOP (yellow) STOP mode of the
C7-613
Illuminates
when the C7-613 is not executing user programs.
Flashes
slowly when the C7-613 requests a CPU memory reset.
Flashes
rapidly when the C7-613 is performing a CPU memory
reset.
3.3
Arrangement of Additional S7-300 Modules
Additional S7-300 Modules
You can connect up to four S7-300 expansion modules to your C7-613 via the
S7-300 I/O bus. These modules can be connected either directly on the device or
at a distance of up to 1.5 m. An IM interface cannot be plugged.
For information on the installation of S7-300 modules, refer to the
S7-300 Automation System Installation: CPU 31xC and CPU 31x
manual.
Summary of Contents for SIMATIC C7-613
Page 14: ...Contents xiv C7 613 Control System A5E00138934 03 ...
Page 56: ...Special Features of the C7 613 3 10 C7 613 Control System A5E00138934 03 ...
Page 90: ...Integration into the User Program 4 34 C7 613 Control System A5E00138934 03 ...
Page 134: ...Maintenance 6 4 C7 613 Control System A5E00138934 03 ...
Page 160: ...A 26 C7 613 Control System A5E00138934 03 ...
Page 176: ...B 16 C7 613 Control System A5E00138934 03 ...
Page 192: ...C 16 C7 613 Control System A5E00138934 03 ...
Page 198: ...Index Index 6 C7 613 Control System A5E00138934 03 ...