Preparing conductors
To connect the individual wires correctly, you need to prepare the individual conductors of
the power supply cable. Proceed as follows:
1.
Select an M10 cable lug for your conductor cross-section.
2.
Strip off the conductor ends so that the remaining insulation reaches up to the cable lug.
3.
Fasten the cable lug correctly to the end of the conductor.
Connecting the conductor
First connect the protective conductor of the power cable before proceeding with the
installation of the remaining conductors. To do this, proceed as follows:
1.
Insert the M10 screws from behind through the square cutouts of the connection rails.
2.
Contact a connection bar with two conductors. Ensure that there is one cable lug on each
side of the copper busbar.
3.
Tighten the fastening nut with the required torque of 40 Nm.
4.
Mark the drawn connections, for example, with a red paint stick.
5.
Replace the protective cover after you have connected all conductors.
Figure 5-11 Connection to the copper bars
Mounting the protective cover
After you have connected all conductors, you need to mount the protective cover again.