Installation and mounting
5.2 Installation location
SICHARGE D
Operating Instructions, 02/2021, 8EM5907-0AA00-1AA7.01
51
Minimum clearances
WARNING
Insufficient ventilation
Insufficient ventilation clearances result in components overheating and, in the worst case,
in the generation of smoke and fire. Severe injuries could result.
Furthermore, the service life of installed components is reduced significantly by excess
temperatures.
To enable operation and maintenance and to ensure proper ventilation of the charging
station, you need to maintain the following minimum clearances:
Figure 5-1
Minimum clearances of SICHARGE D, top view
However, we recommend installing the charging station free-standing as far as possible. If
two charging stations are installed next to one another, double minimum clearances apply
between the two devices.
In addition, a minimum clearance of 20 cm between the top of the charging station and the
ceiling of the room is required at the intended location. Depending on the conditions on site
and your planned procedure for setting up the charging station, the minimum clearance that
you require could be greater for assembly reasons.