Error messages
9.3 Error messages of the RF182C
RF182C communication module
Operating Instructions, 10/2010
75
Error code
ASCII hex
Flashing of
ERR LED
1)
Description
0019
25x
Previous command is active or buffer overflow
The user sent a new command to the communication module although the last
command was still active.
•
Active command can only be terminated with RESET.
•
Two client calls were parameterized with the same parameters
•
Start RESET after error correction
•
When command repetition is used, no data is fetched from the MDS. The data buffer
on the communication module has overflowed. MDS data have been lost.
001C
28x
The antenna of the write/read device is turned off. An MDS command to the
communication module was started in this state.
•
Turn on the antenna with the command "antenna on/off."
•
The antenna is turned on (off) and has received an additional turn-on (turn-off)
command.
001D
–
More MDSes are in the transmission window than the SLG is capable of processing
simultaneously.
•
Only 1 MDS can be processed at a time with a client
001E
30x
Error when processing the function
•
Communication module defective: The communication module receives wrong data
during a RESET
001F
–
Running command canceled by RESET
•
Communication with the MDS was terminated by RESET
•
This error can only be reported if there is a RESET
1)
The flashing ERR-LED can be implemented either on the communication module or on the reader.