Error messages
9.3 Error messages of the RF182C
RF182C communication module
72
Operating Instructions, 10/2010
9.3
Error messages of the RF182C
Table 9- 1
Error messages of the RF182C via the "resultCode" variable
Error code
ASCII hex
Flashing of
ERR LED
1)
Description
0000
–
No error
Default value if everything is ok.
1x
No error
The communication module has executed a start-up and is waiting for a RESET
command.
0001
2x
Presence error: The MDS has moved out of the write/read device's transmission
window. The MOBY command was executed only partially.
Read command: No data is being transmitted to the client.
Write command: The MDS which just left the field contains an incomplete data set.
•
Distance between write/read device and MDS not adhered to
•
Configuration error: The data set to be processed is too large (in dynamic mode)
The next command is automatically executed on the next MDS. A read or write
command is possible.
•
With timeout: No MDS in field
0002
2x
Presence error: An MDS has passed by a write/read device without being processed by
a MOBY command.
This error message is not reported immediately. Instead, the communication module is
waiting for the next command (read, write). This command is immediately replied to with
this error. This means that a read or write command is not processed. The next
command is executed normally again by the communication module.
A RESET command from the client also resets this error state.
Bit 2 is set in the reset parameter option_1, or a reset command was sent and there is
no MDS in the transmission window.
0003
3x
Error in the connection to the write/read device. Write/read device does not answer.
•
The cable between communication module and SLG is wired incorrectly or there is a
cable break
•
The 24 V supply voltage is not connected or is not on or has failed briefly
•
Automatic fuse on the communication module has blown
•
Hardware defective
•
Another SLG is in the vicinity and is active
•
Interference injection on SLG line
•
Execute a RESET command after error correction
0004
4x
Error in MDS's memory
The MDS has never been write-accessed or has lost the contents of its memory due to
battery failure.
•
Replace MDS (if battery bit is set).
•
Install MDS with the STG.
•
Reinitialize MSD (see Section "Command parameter settings").