Page EN-8
Pointek CLS200/300 (Digital) – QUICK START MANUAL
Pointek CLS200/300 (Digital) – QUICK START MANUAL
7ML19985XA02
A
ppendix
C:
m
e
nu c
h
a
rt
Quick Reference: operating functions using input keypad
Function,
(parameter in PDM)
Mode
Key function
Display/ explanation
M
1
1.
Press
to store numerical values; press M to store a selection (indicated by asterisk *).
and
Measured value display
2
2.
L appears in Mode indicator field if HW Write Protection is enabled.
Default startup display; or if Sensor selected in Mode 13
Error display
Error, if transmitter is disturbed
Sensor test
2
*
Either key activates test
Displays GOOD or FAIL D
Rise Time
4
Open Edit mode, or
increment digit.
Move cursor to right, or decrement digit, or
store edited value.
and value (seconds)
Range: 0.0 to 100.0 s
Fall Time
5
Open Edit mode, or
increment digit.
Move cursor to right, or decrement digit, or
store edited value.
and value (seconds)
Range: 0.0 to 100.0 s
HW Write Protection
10
*
Either key enables Write Protection
2
Hold for 5
seconds to
disable
3
3.
If L or LA appear after disabling HW Write Protection, local operation is locked via the bus. Use PDM to disable this lock.
– – = disabled (parameter changes permitted)
L
= enabled (parameter changes inhibited)
Display Source
13
*
Increment or decrement value to make selection
0 = OUT parameter;
1 = primary value;
2 = sensor;
3 = electronics temperature
Unit
14
*
Increment or decrement value to make selection.
Select
o
C;
o
F;
o
R, or K (if 3 selected in Mode 13).
Node address (PROFIBUS
only)
15
Open Edit mode, or
increment digit.
Move cursor to the right, or decrement digit, or
store edited value.
Assign slave address on the PROFIBUS-line (0 to 126)
PROFIBUS Ident Number
16
*
Increment or decrement value to make selection.
Select device mode: according to profile; or, according to profile with full device
specific support.
M
1
and
0% Application Range
setting
19
Open Edit mode, or
increment digit.
Move cursor to the right, or decrement digit, or
store edited value.
Adjust lower limit of application range.
100% Application Range
setting
20
Open Edit mode, or
increment digit.
Move cursor to the right, or decrement digit, or
store edited value.
Adjust upper limit of application range.
Alarm output trigger
23
*
Increment or decrement value to make selection.
Select diagnostic interrupt (dIAG); process interrupt (OUt_d); disabled (OFF): or
diagnostic alarm limit (set in PDM) exceeded (ALErt)
Contact type
24
*
Increment or decrement value to make selection.
Set contact functionality in case of event: (logical inversion of alarm output switch)
- Make contact (CLOSE) / Break contact (OPEn)
Switch Point 1
(Rising Edge)
OFF to ON
25
Open Edit mode, or
increment digit.
Move cursor to the right, or decrement digit, or
store edited value.
Set % of range at which switch will change from OFF to ON. (Hysteresis is a
difference in value between Switch Point 1 and 2).
Switch Point 2
(Falling Edge)
ON to OFF
26
Open Edit mode, or
increment digit.
Move cursor to the right, or decrement digit, or
store edited value.
Set % of range at which switch will change from ON to OFF.
(Hysteresis is a difference in value between Switch Point 1 and 2).
Local Status Text
27
*
Increment or decrement value to make selection.
Select presentation of the status text.
Summary of Contents for Pointek CLS200
Page 1: ...Capacitance Switches Quick Start Manual 09 2010 Pointek CLS200 CLS300 Digital ...
Page 19: ...Page EN 18 Pointek CLS200 300 Digital QUICK START MANUAL 7ML19985XA82 mmmmm English Notes ...
Page 37: ...Side DA 18 Pointek CLS200 300 Digital KVIKSTART MANUAL 7ML19985XA82 mmmmm Dansk Notater ...
Page 55: ...Seite DE 18 Pointek CLS200 300 Digital KURZANLEITUNG 7ML19985XA82 mmmmm Deutsch Notizen ...