Pointek CLS200/300 (Digital) – QUICK START MANUAL
Page EN-15
mm
mm
m
Eng
lis
h
Delay
• Rise Time (Off to On) determines the delay of the signal flow from the moment the sensor
becomes covered until the Primary Value is set.
• Fall Time (On to Off) determines the delay of the signal flow from the moment the sensor
becomes uncovered until the Primary Value is reset.
The delay timers have a range of values from 0.0 to 100.0 seconds.
• Go to Input > Transducer Block: Discrete Input > Delay > Rise Time (Off to On) and set the
value from 0 to 100 seconds.
• Go to Fall Time (On to Off), and set the value from 0 to 100 seconds.
Inversion
When Inversion Output = On, the level status undergoes a logical inversion.
• Go to Output > Function Block: Discrete Input > Inversion Output > Off or On
Failsafe Mode
Go to Output > Function Block: Discrete Input > Fail Safe Mode > Fail Safe Mode and select
one of the three options:.
Resetting
Open the Device Menu Master Reset and select one of the three options:
Factory Reset (restart/cold startup)
Recreates the delivery status. It resets most parameters to the factory setting.
Warm start (new start-up)
Disconnects then restarts Pointek CLS200/300. Communication is interrupted and re-
established. Use it if, for example, the PROFIBUS address has been changed.
Resetting the PROFIBUS address to 126
Please see the full manual for details.
Note:
If the sensor status changes before the delay interval is complete, the timer is reset to
its initial value and restarted.
Failsafe Mode
Description
The default value is used as the output
value.
The predefined preset safety value is output (status code
U_075).
Store the last valid output value.
The last valid output value is output (status code U_071).
The calculated output value is incorrect.
The bad output value is accompanied by the status which
the Transducer block assigns to it (B_0xx).
Summary of Contents for Pointek CLS200
Page 1: ...Capacitance Switches Quick Start Manual 09 2010 Pointek CLS200 CLS300 Digital ...
Page 19: ...Page EN 18 Pointek CLS200 300 Digital QUICK START MANUAL 7ML19985XA82 mmmmm English Notes ...
Page 37: ...Side DA 18 Pointek CLS200 300 Digital KVIKSTART MANUAL 7ML19985XA82 mmmmm Dansk Notater ...
Page 55: ...Seite DE 18 Pointek CLS200 300 Digital KURZANLEITUNG 7ML19985XA82 mmmmm Deutsch Notizen ...