Pointek CLS200/300 (Digital) – QUICK START MANUAL
Page EN-13
mm
mm
m
Eng
lis
h
Quick Setup
Initial setup can be carried out prior to mounting into the process, but it is extremely important
to calibrate the unit and adjust the sensitivity on the product itself.
Adjust 0 % application range setting
CLS200 Digital
1.
Install the device in the process.
2. Open
the
menu
View – Display and select the tab Transducer Block: Discrete Input
(Part 1). Make a note of the Sensor Value (digits) when the device is in the setup
condition that most closely represents the process (refer to table above).
3.
Subtract 300 counts from the Sensor Value noted in step 2 and enter this new value in the
parameter view field: > Input > Transducer Block: Discrete Input > Range of Application>
0%.
CLS300 Digital
1.
Install the device in the process.
1.
Open the menu View – Display and select the tab Transducer Block: Discrete Input
(Part 1). Make a note of the Sensor Value (digits) when the device is in the setup
condition that most closely represents the process (refer to table above).
2.
Enter the sensor value in the parameter view field: > Input > Transducer Block: Discrete
Input > Range of Application> 0%.
WARNING: It is essential to check settings during the process itself, and confirm
that they are correct, before regular operation commences.
Note:
After adjusting values, download data to the device, then go to View – Display to track
the effects.
Application
Material
Setup conditions
General
applications
dry solids
low viscosity liquids
Sensor uncovered and a minimum of 100 mm (4")
free space all around
Demanding
applications
hygroscopic / wet solids
high viscosity and high
conductivity liquids
Sensor immersed and then uncovered, but
retaining as much build up of material as possible
on the sensor.
Interface
detection
liquid A / liquid B
foam / liquid
Immerse the sensor in the material that has the
lowest dielectric constant.
Summary of Contents for Pointek CLS200
Page 1: ...Capacitance Switches Quick Start Manual 09 2010 Pointek CLS200 CLS300 Digital ...
Page 19: ...Page EN 18 Pointek CLS200 300 Digital QUICK START MANUAL 7ML19985XA82 mmmmm English Notes ...
Page 37: ...Side DA 18 Pointek CLS200 300 Digital KVIKSTART MANUAL 7ML19985XA82 mmmmm Dansk Notater ...
Page 55: ...Seite DE 18 Pointek CLS200 300 Digital KURZANLEITUNG 7ML19985XA82 mmmmm Deutsch Notizen ...