Page EN-4
Pointek CLS200/300 (Digital) – QUICK START MANUAL
7ML19985XA82
mm
mm
m
E
n
glis
h
• CLS200 pressure (vessel):
- rod version
-1 to 25 bar g/-14.6 to 365 psi g
- cable version
-1 to 10 bar g/-14.6 to 150 psi g
• CLS300 temperature
1
:
- rod/cable version
-40 to +200 °C (-40 to +185 °F)
- high-temperature version -40 to +400 °C (-40 to +752 °F)
• CLS300 pressure (vessel):
-1 to 35 bar g/-14.6 to 511 psi g
Power
Bus voltage
• General purpose
12 to 30 V DC, 12.5 mA
• Intrinsically Safe
12 to 24 V DC, 12.5 mA
Installation
Mounting Location
• Do:
provide a sun shield to protect the transmitter from direct heat radiation.
• Do not: exceed the permissible ambient temperature limits.
• Do not: mount Pointek CLS200/300 in locations subject to strong vibrations (if it can be
avoided).
Pointek CLS200/300 (standard probe length): top or side mounting
High level alarm
• normally mounted into the vessel top, or
• through the tank wall at the detection level
1.
At process connection.
Notes:
• Installation shall only be performed by qualified personnel and in accordance with local
governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding procedures.
• The housing may only be opened for maintenance, local operation, or electrical
installation.
• Before installing the instrument, verify that the environment complies with any restrictions
specified on the device nameplate.
Notes:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 100 mm (4") between them, to prevent interference
(mount diagonally if space is restricted).
normal process
level
normal process
level
vertical
horizontal
Summary of Contents for Pointek CLS200
Page 1: ...Capacitance Switches Quick Start Manual 09 2010 Pointek CLS200 CLS300 Digital ...
Page 19: ...Page EN 18 Pointek CLS200 300 Digital QUICK START MANUAL 7ML19985XA82 mmmmm English Notes ...
Page 37: ...Side DA 18 Pointek CLS200 300 Digital KVIKSTART MANUAL 7ML19985XA82 mmmmm Dansk Notater ...
Page 55: ...Seite DE 18 Pointek CLS200 300 Digital KURZANLEITUNG 7ML19985XA82 mmmmm Deutsch Notizen ...