The following data points can be operated depending on connected bus device and
configuration.
Supported data
Data point text in SMS
Description
Input values
OptgMode_HC1
Operating
mode
heat
circuit 1
Protection, Automatic,
Reduced, Comfort
OptgMode_HC2
Operating
mode
heat
circuit 2
Protection, Automatic,
Reduced, Comfort
OptgMode_HC3
Operating mode HC3/P
Protection, Automatic,
Reduced, Comfort
DHW_OptgMode
DHW operating mode
Off, On
RoomTemp_ComfSetp_HC1
Room temperature Comfort setpoint HC1
e.g. 20.0 C
RoomTemp_ComfSetp_HC2
Room temperature Comfort setpoint HC2
e.g. 20.0 C
RoomTemp_ComfSetp_HC3
Room temperature Comfort setpoint HC3/P
e.g. 20.0 C
DHW_NomSetp
DHW temperature nominal setpoint
e.g. 60.0 C
RmTmp_act_val_HC1
Room temp actual value heat circuit 1
RmTmp_act_val_HC2
Room temp actual value heat circuit 2
RmTmp_act_val_HC3
Room temperature actual value HC3/P
DHW_TempActTop_B3/BMU
DHW
temperature actual value top (B3)
Outside_temp
Outside
temp
Error_signal
Error
signal
Maintenance_message
Maintenance
message
Reset_HP
Reset heat pump
No, Yes
•
The available values of the connected bus device can be checked up in the
menu "Home > bus device > SMS" of the web operation.
•
Text messages (data point texts and entry values) are written in the language
set on the web server (see menu "Home > 0.5 OZS164.23 > Settings > SMS
operation").
•
When entering text messages, spaces in the data point texts must be replaced
with an underscore "_".
Example: The data point text "DHW TempActTop B3/BMU" from the "SMS"
menu must be entered in the text message as "DHW_TempActTop_B3/BMU".
•
Texts are displayed in the "SMS" menu for the bus device in the language of the
logged on user (see "User accounts" in primary navigation). The user language
must be adapted to the web server language to get to the currently active data
point texts for the web server.
63 / 108
Siemens Web
server
CE1C5711en
Building Technologies
SMS operation
25.08.2010