Path: Home > 0.5 OZS164.23 > Settings > SMS operation
SMS operation
Web server OZS164.23 is needed for remote operation using SMS.
Note
Data point
Explanation, example
Permitted phone number
…5
1
Default val.: 1: *, 2…5: blank
Setting val:
Phone number
(Format: +<int. area code>…)
Phone numbers capable of operation via text
messaging.
Wildcards (*) allow for groups of numbers
(e.g. +41* for all calls from Switzerland). If at
least one entry has a wildcard, access
generally is unlimited.
If e.g. all entries are blank, i.e. without valid
phone number, access is blocked.
Note : We recommend limiting access to
void misuse.
a
—
P
assword
Default val.: 1234
Setting val:
Max. 20 characters
Password for text messaging operation.
Letters and numbers only for password (no
special characters allowed).
The setting remains blank for operation
without password.
Note : We recommend setting a password
o avoid misuse.
t
—
L anguage
Default val.: English
Setting val.: Other languages
Web server language.
The language set is applied to web server
fault text messages, message history,
messages and system reports, and SMS
messages.
Can also be changed via "… > Settings >
eb server".
W
—
S
ession timeout
Default val.: 5 minutes
Setting val:
1-30 minutes
Timeout during which SMS operation is
locked for other users.
The Session timeout is restarted with each
MS accepted.
S
—
29 / 108
Siemens Web
server
CE1C5711en
Building Technologies
Commissioning
25.08.2010