
Specifications
8
Technical data for heat detectors HI110 / HI112
55
Building Technologies
A6V10316298_e_en_--
Fire Safety
2014-05-21
Ambient conditions
Operating temperature/permissible
ambient temperature:
l
HI110
-10…+50 °C
l
HI112 with 'A2S' parameter set
-10…+50 °C
l
HI112 with 'B' parameter set
-10…+65 °C
Storage temperature
-30…+70 °C
Air humidity
≤
95 % rel.
Protection categories according to
EN 60529 / IEC 60529:
l
Bases DB110, DB110x, DB110xx
(all installation types)
IP40
l
Bases DB110, DB110x, DB110xx with
detector base seal RS720
IP42
l
Bases DB110, DB110x, DB110xx with
base attachment wet BA721
IP44
Electromagnetic compatibility:
l
10 kHz…1.8 GHz
50 V/m
l
1.8 GHz…2.5 GHz
20 V/m
Mechanical data
Color
∼
RAL 9010 pure white
Standards
European standards
EN 54-5