8
Specifications
Technical data for smoke detector OP110
52
Building Technologies
A6V10316298_e_en_--
Fire Safety
2014-05-21
Ambient conditions
Operating temperature/permissible
ambient temperature
-10…+50 °C
Storage temperature
-30…+70 °C
Air humidity
≤
95 % rel.
Protection categories according to
EN 60529 / IEC 60529:
l
Bases DB110, DB110x, DB110xx
(all installation types)
IP40
l
Bases DB110, DB110x, DB110xx
with detector base seal RS720
IP42
l
Bases DB110, DB110x, DB110xx
with base attachment wet BA721
IP44
Electromagnetic compatibility:
l
10 kHz…1.8 GHz
50 V/m
l
1.8 GHz…2.5 GHz
20 V/m
Mechanical data
Color
∼
RAL 9010 pure white
Standards
European standards
l
CEA 4021
l
EN 54-7
8.2 Technical data for smoke detector OP110
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
l
Document A6V10301051
Detector line
Operating voltage
DC 16…28 V
Maximum current connection factor
1
Quiescent current at maximum current
connection factor
Max. 100
μ
A
Surge current at maximum current
connection factor
160
μ
A
Alarm voltage at:
l
Alarm current = 1…15 mA
DC 5…10 V
l
Alarm current = 35 mA
DC 18…22 V
l
Alarm current = 50 mA
DC 26…28 V
Alarm current at operating voltage
UB = DC 5…28 V
4…50 mA
Reset voltage UR:
l
Alarm is reliably reset
DC 0…2 V
l
Alarm may possibly not be reset
DC 2…4 V
Protocol
Collective (with and without current limitation)
Compatibility
See 'List of compatibility'
External alarm indicators
Number of external alarm indicators that
can be connected
Max. 2
Voltage
DC 9…30 V
Current
10…16 mA