Structure and function
3
Function
21
Building Technologies
A6V10316298_e_en_--
Fire Safety
2014-05-21
Heat detector HI110
Color
Parameter set
Flashing frequency
Meaning
Red
'A1R'
One flash every 1 s
Alarm
Yellow
'A1R'
One flash every 10 s
Fault
Green
'A1R'
During the first 15 minutes of
operation:
One flash every 5 s
l
No fault
l
Operation with 'A1R'
parameter set
Heat detector HI112
Color
Parameter set
Flashing frequency
Meaning
Red
'A2S' and 'B'
One flash every 1 s
Alarm
Yellow
'A2S' and 'B'
One flash every 10 s
Fault
Green
'A2S'
During the first 15 minutes of
operation:
One flash every 5 s
l
No fault
l
Operation with 'A2S'
parameter set
Green
'B'
During the first 15 minutes of
operation:
Two flashes every 5 s
l
No fault
l
Operation with 'B'
parameter set
See also
2
3.3.4 Connection for external alarm indicators
A maximum of two external alarm indicators can be connected to each point
detector.
See also
2
3.3.5 Test mode
Optical detectors can be tested with the test gas REF8 or REF8-S. Heat detectors
can be tested with a hot air fan.
Once the detector line has been started up or reset, the smoke detector OH110
has a reduced response time in the 'Robust' parameter set for a period of
3 minutes. It is possible to test the point detector with test gas during this period.
Simplified test readiness of the point detector is indicated by the green LED
flashing three times every 10 s.
See also
2
2