Planning
4
Compatibility
29
Building Technologies
A6V10316298_e_en_--
Fire Safety
2014-05-21
4 Planning
4.1 Compatibility
Compatible with control panels which support collective operation or conventional
operation on the detector line.
You will find details in the 'List of compatibility'.
4.2 Multi-sensor fire detector
Like all optical smoke detectors, the multi-sensor fire detector OH110 is able to
detect slow-burning fires that generate smoke.
However, when compared to standard optical smoke detectors, the multi-sensor
fire detector OH110 also offers improved response behavior in the event of open
fires and increased resistance to misleading sources of false alarms.
The multi-sensor fire detector OH110 has two selectable parameter sets.
4.2.1 Parameter sets
Robust:
The parameter set 'Robust' offers improved resistance to false alarms in areas
where misleading sources, such as cigarette smoke or exhaust fumes, may cause
these to be triggered.
The parameter set 'Robust' is automatically set if the point detector is installed in
a detector base DB110R or DB110RD.
Sensitive:
This parameter set is particularly suitable for areas where few misleading sources
of false alarms are present, when priority is given to detecting open fires as early
as possible.
The parameter set 'Sensitive' is automatically set if the point detector is installed
in a detector base DB110 or DB110D.