Specifications
8
Technical data for smoke detector OP110
53
Building Technologies
A6V10316298_e_en_--
Fire Safety
2014-05-21
Device characteristics
Response sensitivity
at 0.2 m/s (typ.)
1.8 or 2.5 %/m (depending on the parameter
set)
Permissible wind speed
Max. 5 m/s
Compensation speed
≤
1/45 voltage increase for detection/h
Flashing interval times AI:
See chapter 'Internal alarm indicator'
Connections
Detector line and external alarm
indicators:
l
Design
Screw terminal
l
Cable cross section
2 x 0.2…1.6 mm
2
Ambient conditions
Operating temperature/permissible
ambient temperature
-10…+50 °C
Storage temperature
-30…+70 °C
Air humidity
≤
95 % rel.
Protection categories according to
EN 60529 / IEC 60529:
l
Bases DB110, DB110x, DB110xx
(all installation types)
IP40
l
Bases DB110, DB110x, DB110xx with
detector base seal RS720
IP42
l
Bases DB110, DB110x, DB110xx with
base attachment wet BA721
IP44
Electromagnetic compatibility:
l
10 kHz…1.8 GHz
50 V/m
l
1.8 GHz…2.5 GHz
20 V/m
Mechanical data
Color
∼
RAL 9010 pure white
Standards
European standards
EN 54-7