Mounting / Installation
5
Cable entry
43
Building Technologies
A6V10316298_e_en_--
Fire Safety
2014-05-21
5.8 Cable entry
The detector bases DB110, DB110x and DB110xx feature four screw terminals. A
maximum of 2 cables may be connected to each screw terminal.
The cable cross section of the screw terminals is 0.2…1.6 mm
2
.
Terminal name
Connection
1a
+Connection for external alarm indicator
1b
+Collective detector line IN and OUT
5
-Collective detector line IN (from the control panel) / -
external alarm indicator
6
-Collective detector line OUT (from the EOL) / -external alarm
indicator
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
●
The cable loops must be placed flat in the base bottom.
●
The bare length of the cables is approximately 8…10 mm.
5.8.1 Auxiliary terminals DBZ1190-AA/-AB
Use the following auxiliary terminals for multiple connections:
l
DBZ1190-AB connection terminal 1…2.5 mm²
l
DBZ1190-AA micro terminal 0.28…0.5 mm²
Detector base with connection terminals and micro terminals