Mounting / Installation
5
Detector base (collective) DB110 / DB110x / DB110xx
35
Building Technologies
A6V10316298_e_en_--
Fire Safety
2014-05-21
5.2 Detector base (collective)
DB110 / DB110x / DB110xx
l
Install the detector base directly on the ceiling.
l
Insert the cables into the detector base. You have the option of using the
following types of line:
– Recess-mounted cable entry
– Surface-mounted cable entry (cable diameter max. 8 mm)
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
●
The cable loops must be placed flat in the base bottom.
●
The bare length of the cables is approximately 8…10 mm.
1
2
1
Minimum Ø 40 mm
2
Maximum Ø 90 mm
Use the detector bases DB110D and DB110RD if you are installing a fire
detection system in accordance with BS 5839, part 1.