Connecting
5.6 Sensor Wiring
FUG1010 IP65 NEMA 4X
Operating Instructions, 01/2013, A5E02951519-AC
83
Clamp-on Sensors
Clamp-on style sensors are mounted on the surface of the monitored pipe using series
mounting assemblies. Apply a generous quantity of the thermal couplant provided to the tip
of the sensor and attach it securely to the cleaned pipe surface with the proper mounting
assembly. Temperature measurement anomalies resulting from variations in the ambient
conditions can be minimized by insulating the pipe and sensor after installation.
①
Temperature Sensor Connector Head
Assembly
⑤
Thermal Couplant
②
7ME39600CR 992EC Series Cable
⑥
Spring Loaded Sensing Element
③
Threaded Pipe Fitting
⑦
Pipe Wall
④
Thermowell
Figure 5-27 Insert Temperature Sensor
Insert sensors are designed to be used in pipes equipped with Thermowells. These are
spring-loaded, 1/4" diameter sensors with 1/2" NPT integral connection heads, available in
several lengths to accommodate a range of pipe sizes.
Proceed to Commissioning (Page 85).
5.6
Sensor Wiring
Connecting Sensors to the Transmitter
1.
Open the transmitter top cover. Using a flat blade screwdriver, remove the Cable Strain
Relief bracket (see figure below).
2.
Observing the upstream and downstream orientation, attach the UP (upstream) and DN
(downstream) cables to the sensors and make snug. Attach the other ends to the UP and
DN terminals of the flow meter (see figure below).
Summary of Contents for FUG1010 IP65 NEMA 4X
Page 9: ...Table of contents FUG1010 IP65 NEMA 4X 8 Operating Instructions 01 2013 A5E02951519 AC ...
Page 196: ......
Page 197: ......
Page 198: ......
Page 199: ......
Page 200: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ...21614 C 1011NFPS 7 ...
Page 238: ...1011NFPS 7 C 21614 ...
Page 239: ...1011NFPS 7 C 21614 ...
Page 240: ...21614 C 1011NFPS 7 ...
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ...21614 C ...
Page 247: ......
Page 248: ......
Page 249: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 250: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 251: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 252: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 253: ......
Page 254: ......
Page 255: ......
Page 256: ......
Page 257: ......
Page 258: ......
Page 266: ...Glossary FUG1010 IP65 NEMA 4X 200 Operating Instructions 01 2013 A5E02951519 AC ...
Page 270: ...Index FUG1010 IP65 NEMA 4X 204 Operating Instructions 01 2013 A5E02951519 AC ...