Functions
7.11 Setting Relays
FUG1010 IP65 NEMA 4X
Operating Instructions, 01/2013, A5E02951519-AC
131
7.11
Setting Relays
Relay Functions
Use the [Relay Setup] menu to assign a function to channel relays. The flow meter supports
two types of relay outputs, Alarm Relay and Pulse Relay. Alarm Relay outputs operate in
"fail-safe" mode. The relay(s) are energized under normal conditions - an alarm condition
causes the relay(s) to de-energize until the alarm clears. The Pulse Relay output supports
Totalizer and batch relay functions, with an output pulse width of approximately 200 ms;
maximum activation rate is 2.5 pulses per sec. If Totalizer pulses exceed this rate, excess
pulses are stored in an overflow register. This allows the relay to "catch up" when flow
decreases enough.
Note
Using the <F1> key (Totalizer clear command) also clears all channel Totalizers plus the
overflow register described in the last paragraph.
Relay 1, 2, 3, and 4 Function Assignments
The flow meter, depending upon the model, provides four alarm relays. Please refer to the
Appendix A for wiring details. Relays respond to any of the alarm conditions or data
functions included on the Relay Option List.
Table 7- 14 Relay Option List
Not Used
Not Active
Power Off
Power Off alarm occurs when power fails.
S S.G.
Specific Gravity value relay trip-point.
S Base S.G.
S.G. value relay trip-point at reference temperature.
S High Visc
Kinematic viscosity (centistokes) exceeds High Setpoint.
S Low Visc
Kinematic viscosity (centistokes) falls below Low Setpoint.
S High Temp.
High temperature value relay trip-point.
S Low Temp.
Low temperature value relay trip-point.
S High Flow
Flow rate exceeds high flow set point.
S Low Flow
Flow rate falls below low flow set point.
S Flow Alarm
Flow rate exceeds or falls below flow set points.
S Fault Alarm
Loses receive signal (all paths in fault).
S Spacing
Sensor spacing needs adjusting.
S Turbulence
Turbulence percentage exceeds alarm setpoint.
S Interface
Interface setpoint exceeded.
S Reverse Flow
Flow is in negative direction.
S BatchTot
Batch/Sample total advances.
S Pos Total
Positive total volume advances 1 digit.
S Neg Total
Negative total volume advances 1 digit.
Summary of Contents for FUG1010 IP65 NEMA 4X
Page 9: ...Table of contents FUG1010 IP65 NEMA 4X 8 Operating Instructions 01 2013 A5E02951519 AC ...
Page 196: ......
Page 197: ......
Page 198: ......
Page 199: ......
Page 200: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ...21614 C 1011NFPS 7 ...
Page 238: ...1011NFPS 7 C 21614 ...
Page 239: ...1011NFPS 7 C 21614 ...
Page 240: ...21614 C 1011NFPS 7 ...
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ...21614 C ...
Page 247: ......
Page 248: ......
Page 249: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 250: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 251: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 252: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 253: ......
Page 254: ......
Page 255: ......
Page 256: ......
Page 257: ......
Page 258: ......
Page 266: ...Glossary FUG1010 IP65 NEMA 4X 200 Operating Instructions 01 2013 A5E02951519 AC ...
Page 270: ...Index FUG1010 IP65 NEMA 4X 204 Operating Instructions 01 2013 A5E02951519 AC ...