Faults / Troubleshooting
10
174 | 184
Building Technologies
A6V10211076_i_en_--
Fire Safety
2015-12-15
10 Faults / Troubleshooting
If the ↑ site displays 'Fault', you will find in the table below a list with possible
'Faults' including information on possible causes.
If a 'Fault' cannot be rectified with the help of these operation instructions, please
contact the service engineer.
'Fault'
Cause
Remedy
Automatic detector
Detector is missing Re-insert detector
Detector is out of
order
Replace the detector.
NOTICE! Any defective detector must always be replaced
by another detector of the same type.
Manual call point
Glass pane broken Replace glass pane
Other damages
Contact service provider
Mains failure
Mains failure in the
public network
No action required.
Emergency power supply is ensured by batteries during at
minimum 12 hours; depending on the customer
specification up to 72 hours.
Fuse damaged
Check fuses (current distributor of the building) and replace
them if necessary.
Paper out
Paper roll in the
printer has been
used up
Insert printing paper
With all other 'Faults', the service provider in account must be contacted.
See also
1