System functions
Visibility
6
118 | 184
Building Technologies
A6V10211076_i_en_--
Fire Safety
2015-12-15
6.8.1 PIN input dialog
The 'Login/logout' main menu item opens the PIN input dialog. The access level in
account is released by entering a valid PIN.
The PIN input dialog is indicated automatically if the activation of a button on the
↑ PMI requires a higher access level.
6.8.2 Logout timeout
The ↑ 'Station' is provided with a time control function for the operation.
The operation enable for an 'Access level' expires after a configurable period of
time has passed since the last entry.
See also
1
Log in / Change access level [➙ 58]
6.9 Visibility
Several fire control panels and fire terminals ('Stations') can be integrated into a fire
detection installation. The ↑ visibility defines which part of a fire detection
installation on ↑ 'Station' is visible and can be operated.
The ↑ visibility is configured in Cerberus-Engineering-Tool.
The visibility for a fire control panel can be configured in the following topology
levels of a fire detection installation:
● ↑ 'Site'
● ↑ 'Station'
● 'Area'
The visibility for this 'Station' is configured by selecting and assigning event
categories from the topology to the visibility for this 'Station'.
For example, all the 'ALARMS' for the 'Site' or just the 'Faults' for the 'Area' of a
'Station' are indicated.
Two other modes are available for configuring the ↑ visibility:
● 'PMI standby visibility'
● 'PMI expanded visibility'
See also
1
1