ECO REFERENCE MANUAL
12-4
EMC
Class 2: Filtered Industrial
This level of performance will allow the manufacturer/assembler to self-certify their apparatus for
compliance with the EMC directive for the industrial environment as regards the EMC performance
characteristics of the power drive system. Performance limits are as specified in the Generic Industrial
Emissions and Immunity standards EN 50081-2 and EN 50082-2.
EMC Phenomenon
Standard
Level
Emissions:
Radiated Emissions
EN 55011
Level A1
Conducted Emissions
EN 55011
Level A1
Immunity:
Supply Voltage Distortion
IEC 1000-2-4 (1993)
Voltage Fluctuations, Dips, Unbalance,
Frequency Variations
IEC 1000-2-1
Magnetic Fields
EN 61000-4-8
50 Hz, 30 A/m
Electrostatic Discharge
EN 61000-4-2
8 kV air discharge
Burst Interference
EN 61000-4-4
2 kV power cables, 2 kV control
Radio Frequency Electromagnetic Field,
amplitude modulated
ENV 50 140
80-1000 MHz, 10 V/m, 80% AM,
power and signal lines
Radio Frequency Electromagnetic Field,
pulse modulated
ENV 50 204
900 MHz, 10 V/m 50% duty cycle,
200 Hz repetition rate
Class 3: Filtered - for residential, commercial and light industry
This level of performance will allow the manufacturer / assembler to self-certify compliance of their
apparatus with the EMC directive for the residential, commercial and light industrial environment as
regards the EMC performance characteristics of the power drive system. Performance limits are as
specified in the generic emission and immunity standards EN 50081-1 and EN 50082-1.
EMC Phenomenon
Standard
Level
Emissions:
Radiated Emissions
EN 55022
Level B1
Conducted Emissions
EN 55022
Level B1
Immunity:
Electrostatic Discharge
EN 61000-4-2
8 kV air discharge
Burst Interference
EN 61000-4-4
1 kV power cables, 0.5 kV control
The MICROMASTER Eco and MIDIMASTER Eco units are intended exclusively for
professional applications. Therefore, they do not fall within the scope of the harmonics