ECO REFERENCE MANUAL
13-7
Automatic re-start after
mains break
0 -1
[1]
0 = No re-start after mains break - run
signal must be re-generated
1 = Automatic re-start after mains break if
run signal is present
Automatic restart after fault
0 - 1
[0]
Automatic restart after fault:
0 = Disabled
1 = The inverter will attempt to restart up to
5 times after a fault. If the fault is not
cleared after the 5th attempt, the
inverter will remain in the fault state.
The display flashes during this
condition.
WARNING:
While waiting to re-start, the display will
flash. This means that a start is pending and
may happen at any time. Fault codes can be
observed in P930.
Skip frequency bandwidth
(Hz)
0.0 - 10.0
[2.0]
Frequencies set by P014, P027, P028 and
P029 that are /- the value of P019 of
all skip frequencies are suppressed.
Minimum analogue
frequency (Hz)
0 - 150.0
[0.0]
Frequency corresponding to the lowest
analogue input value, i.e.0 V/0 mA or 2 V/4
mA, determined by P023 and the settings of
the DIP selector switches 1, 2 and 3 (
see
the DIP Selector Switches figure in this
section).
This can be set to a higher value
than P022 to give an inverse relationship
between analogue input and frequency
output
(see diagram in P022)
.
Maximum analogue
frequency (Hz)
0 - 150.0
[50.0]
(60)North
America
Frequency corresponding to the highest
analogue input value, i.e.10 V or 20 mA,
determined by P023 and the setting of the
DIP selector switches 1, 2 and 3 (
see the
DIP Selector Switches figure in this section).
This can be set to a lower value than P021
to give an inverse relationship between
analogue input and frequency output. i.e.
f
V/ I
P021
P021
P022
P022
Note: The output frequency is limited by
values entered for P012/P013.