ECO REFERENCE MANUAL
13-18
Drive model
0 - 47
[
¶¶¶
]
Read-only parameter; indicates the power
rating according to the type range indicated
by P112.
P113
P112 =9
P112=10
P113
P112=10
0
ECO110/2
26
ECO5500/3
1
ECO150/2
27
ECO7500/3
2
ECO220/2
28
ECO9000/3
3
ECO300/2
29
ECO11000/3
4
ECO400/2
30
ECO13200/3
5
ECO110/2
ECO550/2
31
ECO16000/3
6
ECO150/2
ECO750/2
32
ECO20000/3
7
ECO220/2 ECO1100/2
33
ECO25000/3
8
ECO300/2 ECO1500/2
34
ECO31500/3
9
ECO400/2 ECO1850/2
35
10
ECO2200/2
36
ECO220/4
11
ECO3000/2
37
ECO300/4
12
ECO3700/2
38
ECO400/4
13
ECO4500/2
39
ECO550/4
14
ECO110/3
40
ECO750/4
15
ECO150/3
ECO300/3
41
ECO1100/4
16
ECO220/3
ECO400/3
42
ECO1500/4
17
ECO300/3
ECO550/3
43
ECO1850/4
18
ECO400/3
ECO750/3
44
ECO2200/4
19
ECO550/3 ECO1100/3
45
ECO3000/4
20
ECO750/3 ECO1500/3
46
ECO3700/4
21
ECO1850/3
47
ECO4500/4
22
ECO2200/3
23
ECO3000/3
24
ECO3700/3
25
ECO4500/3
Enable/disable RUN button
0 - 1
[1]
0 = RUN button disabled
1 = RUN button enabled (only possible if
P007 = 1)
Enable/disable
∆
and
∇
buttons
0 - 1
[1]
0 =
∆
and
∇
buttons disabled
1 =
∆
and
∇
buttons enabled (only possible
if P007 = 1)
This applies for frequency adjustment only.
The buttons can still be used to change
parameter values.
Fan switch-off delay time
(seconds) (MMV only)
0 - 600
[120]
Time taken for the fan to switch off following
an OFF command.