ECO REFERENCE MANUAL
13-10
Value
Function of P051 to P055 and P356
Function,
low state
(0V)
Function,
high state
(>10V)
0
Input disabled
-
-
1
On right
Off
On right
4
OFF2
OFF2
On
5
OFF3
OFF3
On
6
Fixed frequencies 1-6
Off
On
9
USS operation (P910 = 1 or 3)
Local (see
P006, P007)
USS control
10
Fault reset
Off
Reset on rising edge
11
Increase frequency*
Off
Increase
12
Decrease frequency*
Off
Decrease
13
Switch between analogue input frequency
setting and digital/keypad frequency setting
Analogue
setpoint
Digital setpoint
14
Disable the ability to change parameters
‘P’ enabled
‘P’ disabled
18
Fixed frequencies 1-6, but input high will also
request RUN when P007 = 0
Off
On
19
External trip
Off
On
22
Download parameter set 0 from Ope***
Off
Download
23
Download parameter set 1 from OPe***
Off
Download
24
Switch analogue setpoint
Analogue input
1 active
Analogue input 2
active
*
Only effective when P007 = 0.
**
Not available on P051, P052 or P356.
***
The motor must be stopped before downloading begins.
Downloading takes approx. 30 seconds.