FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_
03
Building Technologies
FNC05 – Four-pipe fan coil with electric reheater
30.11.2007
Application FNC05 includes the following functions
(refer to the description of functions CM110385 for detailed information):
Function
Brief description
)
Four-pipe fan coil.
– PI control.
– Two proportional control sequences, heating and cooling.
– Control of thermal / electromechanic valve actuators
(AC 24 V, PDM or AC 24 V, 2-position).
– Control of motorized KNX bus actuator valves.
– Valve exercising feature.
Electric air heater.
– 2-position or proportional control.
– Control: AC 24 V, 2-position or proportional.
Fan control.
– 1 ... 3-speed
Automatic, or
– Manual with room unit.
Temperature measurement. – Room temperature sensor or
– Return air sensor.
Room operating modes.
– Comfort, Precomfort, Economy and Protection mode..
– Change of operating mode via
/Auto switch on room unit, presence detector,
window contact or central command.
Setpoint shift.
– Locally via room unit or centrally.
General functions.
– Presence detector.
– Window switch.
– Master/slave operation.
– Boost heating, night cooling etc.
– Free inputs/outputs.
Room units.
Available with temperature sensor, setpoint adjuster,
button for
/Auto and fan speed control, and LCD display.
Compatible controllers.
FNC05 is supplied with RXB22.1/FC-12.
Functions