CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Select communications mode
28 Feb 2009
Outside temperature
zone
Zone
= ---, 1...31
The outside temperature is exchanged in this zone (all
Synco 700 devices).
Master/slave zone
(Apartment . Room . Subzone)
Apartment = ---, 1...126
Room
= ---, 0...63
Subzone
= ---, 0...15
In cases where RXB controllers are to be operated in
master/slave mode, a master/slave zone must also be
defined. For the master, it is usual to enter the
geographical zone of the master. The same
master/slave zone is used for the slave as for the
master.
See also "Master/slave", page 94.
Select the menu option
Communication
.
ETS3