CLC & RAD – chilled ceiling and radiator applications from CC-02
14.03.2008
CLC02 – Chilled ceiling and radiator
Application CLC02 includes the following functions
(refer to the description of functions CM110384 for detailed information):
Function
Brief description
Continuous heating and
cooling sequence.
– PI control.
– Two proportional control sequences, heating and cooling.
– Control of thermal / electromechanic / motorized valve actuators (AC 24 V, PDM /
AC 24 V, 2-position / AC 24 V, 3-position).
– Control of motoric KNX bus valve actuators
– Downdraft compensation
– Valve exercising feature.
Dewpoint sensor.
– Dewpoint sensor to prevent condensation.
Temperature measurement. – Via room unit or passive temperature sensor.
Outside temperature (for
downdraft compensation).
– Via KNX bus.
Room operating modes.
–
Comfort, Precomfort, Economy
and
Protection mode.
– Change of operating mode via
/Auto switch on room unit, presence detector,
window contact or central command.
Setpoint shift.
– Locally via room unit or centrally.
General functions.
– Presence detector.
– Window contact.
– Master/slave operation.
– Boost heating, night cooling etc.
– Free inputs/outputs.
Room units.
Versions available with temperature sensor, setpoint shift,
/Auto switch and LCD display.
Compatible controllers.
CLC02 runs on RXB24.1/CC-02
Functions