Building Technologies
Room operating modes
28 Feb 2009
5.6.1
Local control of room operating mode via
a window contact input
Window contact
PPS2
Local
1.
DI
DI
3.
Controller
3.
Prio
If a window is opened, the room controller always switches to
room operating mode
Protection
, i.e. the heating or cooling
output is reduced to a minimum.
The window contact is connected directly to a digital input of the room controller (see
page 102).
The table below shows the
Effective room operating mode
as a function of the
window
contact
input.
Window contact state
Effective room operating mode
No window contact
Comfort
(default)
Window closed
No effect.
Lower-priority inputs determine the operating mode.
Window open
Protection.
5.6.2
Local control of room operating mode via presence
detector
Presence detector
PPS2
Local
1.
DI
DI
3.
Controller
3.
Prio
A presence detector detects the presence of people in the
room and controls the room operating mode of a room
controller.
The presence detector is connected directly to a digital input of the room controller (see
page 102).
Effective room operating
mode