2.1 Mechanical Installation
2.1.1 Mounting the drive
Drill pattern and outline dimensions
Mounting method
Minimum mounting clearance
EN-10 SINAMICS V60 Controlled Power Module (CPM60.1) Getting Started
Installation
You mount the drive with four M5 screws to the inner wall of the cabinet. Note that the drive
must be mounted vertically to the cabinet wall, with the ventilation openings of the drive
pointing upwards. The screw tightening torque of the drive must be no more than 2.0 Nm.
To ensure sufficient heat dissipation, please observe the requirements for minimum
clearance between drives, one drive and another device/inner wall of the cabinet, as
illustrated in the picture below: