5.4 Digital In/Outputs
The digital Inputs and Outputs are floating switches by breaking the contact.
Connecting the digital In/Outputs
The digital In/Outputs contacts are connected to a 4-pin plug-in terminal block.
The digital In/Outputs can be subjected to a maximum load of 50 mA (safety extra low
voltage SRLV 24 VDC).
Pin number
Assignment (24 VDC)
Labeling
DI/DO
In/Output 24 V DC
SGND
Ground for In/Output
SGND
In/Output 24 V DC
DIDO
Ground for In/Output
5.5 Connecting functional ground
Installation on a DIN rail
The device is grounded over the DIN rail.
S7 standard rail
The device is grounded over the rear panel and the neck of the screw.
Wall mounting
The device is grounded by the securing screw in the unpainted hole..
Please note that the BANY Agent must be grounded over one securing screw with
minimum resistance.
If an BANY Agent is mounted on a non-conducting base, a grounding cable must be
installed. The grounding cable is not supplied with the device. Connect the paint-free
surface of the BANY Agent to the nearest grounding point using the grounding cable.
Summary of Contents for BANY Agent
Page 1: ...BANY Agent 1 Compact Operating Instruction SIEMENS BANY Agent Compact Operating Instructions ...
Page 13: ...BANY Agent 13 Compact Operating Instruction Bild 1 BANY Agent mit TAP ...
Page 15: ...BANY Agent 15 Compact Operating Instruction ...
Page 35: ...BANY Agent 35 Compact Operating Instruction 7 Dimension drawings 7 1 BANY Agent with TAP ...
Page 36: ...BANY Agent 36 Compact Operating Instruction ...
Page 37: ...BANY Agent 37 Compact Operating Instruction ...
Page 38: ...BANY Agent 38 Compact Operating Instruction 7 2 BANY Agent without TAP ...
Page 39: ...BANY Agent 39 Compact Operating Instruction ...