2.3. Mounting PV Inverter
Please be sure the installation guidelines listed below are followed,
1.
Select a wall or solid vertical surface that can support the PV-Inverter for the long term.
2.
PV-Inverter requires adequate space for ventilation and heat dissipation. Allow at least 30cm
space above and 90cm space below the Inverter. (Figure 2.3-1).
3.
For maintenance purpose, please keep Inverters at least 30cm distance between inverters.
Ⴃ
Figure 2.3-1 Minimum space requirement
Note:
Don’t mount PV-Inverter on top of another one or other heat radiating source unless it is inevitable,
in that case, 90cm distance at minimum from each other is required to provide proper ventilation.
Ⴃ
Figure 2.3-2 Vertical installation is not suggested
4.
Fix the bracket with screws on all mounting holes with M4*30mm screws and 16kgf-cm (or 1.57
N-m ) torque as illustrated below (Figure 2.3-3):