Figure 2.5-2 AC output connection
(6) An insulated cord end terminal shall be cramped at the end of each AC cable before connecting to
the AC terminal block. The stripped length of AC cable shall be about 9mm to 10mm.
(7) Connect the AC cables to the AC terminal block in accordance with the label (Figure 2.5-3).
.
Ⴃ
Figure 2.5-3 AC terminal block connection
Note: All wires should be firmly fixed with torque 6Kgf-cm or 0.6N-m.
After fixing the AC cables to the AC terminal block, slightly pull the cables one by one and
make sure they cannot be easily pulled off.
(8) Fix the AC output cover back with four M3x15L screws (6Kgf-cm torque at least).
Ⴃ
Figure 2.5-4 AC cover installation