IV352 Rev.02
Date Issue:
2012-10-27
Page 137 di 232 + FR
1.Const. Q
2kVA
&RVIL
3 .:
4 9$5
Cosfi = 0.9
P = 1,8KW
Q= (-)872 Var ~ (+)872 Var
(48.43% P)
3kVA
&RVIL
3 .:
4 9$5
Cosfi = 0.9
P = 2,7KW
Q= (-)1308 Var ~ (+)1308 Var
(48.43% P)
4kVA
&RVIL
3 .:
4 9$5
Cosfi = 0.9
P = 3,6KW
Q= (-)1744 Var ~ (+)1744 Var
(48.43% P)
6kVA
&RVIL
3 .:
4 9$5
Cosfi = 0.9
P = 5,4KW
Q= (-)2615 Var ~ (+)2615 Var
(48.43% P)
2. Const PF
(-)0.90 ~(+)0.90 pf
3. Curve Q(U)with type A&B
P Lock-in: 20% Pn
P Lock-out: 5% Pn
Node1:
90%
(+)43.6% Q/S
Node2:
92%
(+) 0% Q/S
Node3:
108%
(+) 0% Q/S
Node4:
110%
(-)43.6% Q/S
4.Curve PF(P) Type A
V Lock-in: 241.5 V
V Lock-out:230.0 V
Node1:
20%
(+) 1.00pf
Node2:
40%
(+) 1.00pf
Node3:
50% (*note 3)
(+) 1.00pf
Node4:
90%
(-) 0.90pf
Curve PF(P) Type B
Node1:
0%
(+) 1.00pf
Node2:
5%
(+) 1.00pf
Node3:
5%
(-)0.90pf
Node4:
90%
(-) 0.90pf
(1)
CEI 0-21 LV (S1=S2) LV & MV has the same default setting :
V^ = 276V 0,5s, V_ = 184V 1s, F_ = 47Hz 4s, F^ = 52Hz 1s, Slope:2.4%
(2)
In CEI 0-21, Voltage & Frequency operation range & disconnection time setting are adjustable.
S1 Voltage average value of the voltage measured on a time window of 10 min mode moving average
(3)
The inverter must start in any case when the F & V are allocated in 49.9~50.1hz & 195.5 ~253V, (included the first
start)