2.4. AC Cable Selection
AC cable size shall be properly selected basing on maximum wiring length.
(1) To meet safety requirement, use AC output wires with section area of no less than the minimum
required size as indicated in the table below (Table 2.4-1):
L (Phase ); N (Neutral); PE (Protective Earth): 1.5-4mm
2
Minimum
Model
Rating
Section Area
W
mm
2
AWG
SOLEIL
1F-TL2K
2000
1.5
14
SOLEIL
1F-TL3K
3000
2.5
12
SOLEIL
1F-TL4K
4000
2.5
12
SOLEIL
1F-TL6K
6000
4.0
10
Ⴃ
Table 2.4-1 Requirement of AC output wires
Note:
Do not use cables which may cause power loss over 1% of nominal power.