IV319 Rev.00
Data 2010-06-22
Pag. 56 di 118
12. Communication Port
12.1 RS232 Interface
The following is the pin assignment and description of DB-9 connector.
12.2 Intelligent slot
This series is equipped with an intelligent slot for Webpower (optional
accessory) or other optional card to achieve remote management of the
UPS through internet / intranet. Please contact your local distributor for
further information.
12.3 AS400 Interface (Option)
Except for the communication protocol as mentioned above, this series
UPS has AS400 card (an optional accessory) for AS400 communication
protocol. Please contact your local distributor for details. The following is
the pin assignment and description of DB-9 connector in AS400 card.
Pin #
Description
I/O
Pin #
Description
I/O
1
UPS Fail
Output
6
Bypass
Output
2
Summary Alarm
Output
7
Battery Low
Output
3
GND
Input
8
UPS ON
Output
4
Remote Shutdown
Input
9
Line Loss
Output
5
Common
Input
Pin #
Description
I/O
2
TXD
Output
3
RXD
Input
5
GND
Input