Important notes:
If the UPS is used in single mode, JPI and JP2
must be connected by 9AWG or 10mm
2
. If the UPS is used in
parallel mode, JP1 and JP2 must be disconnected.
Important notes:
If the UPS is used in single mode, JPI and JP2
must be connected. If the UPS is used in parallel mode, the Jumper
between JP1 and JP2 must be removed.
2. Backfeed protection
If the UPS does not have an automatic protection device against
current back-feed, the operator/installer must:
- add warning labels to all the mains power disconnecting switches
installed at a distance from the UPS area; this serves to remind
Input and output Terminal Block wiring diagram of 10K 3/1
Input and output Terminal Block wiring diagram of 15K / 20K 3/1