The Fault code is
³
11
´
, the UPS
beeps continuously.
Battery low or battery
not connected.
Check the battery. If the battery is
damaged, replace the battery
immediately and ensure that the
EDWWHU\EUHDNHULVLQ³21´
position.
The utility power is
normal, but the
UPS can not turn
into Line mode
Maintain switch loose
Please contact the distributor or
service center.
Battery discharging
time diminishes
Battery not yet been
fully charged.
Keep UPS connected to utility
power persistently for more than
10 hours to recharge the
batteries again.
UPS overloaded.
Check the loads and remove the
non-critical equipment.
Battery aged.
Replace the batteries. Please
contact the distributor to obtain
the parts and replacement
service.
The UPS cannot
power on after
pressing the ON
button
The ON button is
pressed too briefly.
Press the ON button for more
than 1 second.
The UPS is not
connected to the
battery or the battery
box voltage is too low.
Check the battery or recharge the
battery.
UPS fault.
Please contact the distributor or
service center.
When you contact the service center, please provide the following
information:
Ⴠ
Model No. and the serial No. of the UPS ) it is written in a label under
the barcode present in the UPS back side or UPS cover.
Ⴠ
The date when the problem arise.
Ⴠ
Complete description of the problem, including the LCD display, code,
alarm warning, input power condition and load capacity. If your UPS
is a long backup time model, you may also provide the information
of the external battery box.
Summary of Contents for Green Point 6 20KVA
Page 28: ...IV319 Rev 00 Data 2010 06 22 Pag 28 di 118 Wiring diagram of 6K 10K 1 1 parallel system...
Page 29: ...IV319 Rev 00 Data 2010 06 22 Pag 29 di 118 Wiring diagram of 10K 3 1 parallel system...
Page 57: ...IV319 Rev 00 Data 2010 06 22 Pag 57 di 118 DB 9 Interface of AS400 communication protocol...
Page 61: ...IV319 Rev 00 Data 2010 06 22 Pag 61 di 118 Back View of 15K 20K 3 1...