IV319 Rev.00
Data 2010-06-22
Pag. 33 di 118
2) Upon completion of the above to turn it off, output of electric
current of the UPS is still present. In order to cut off the output
from the UPS, simply cut off the utility power supply, a few
seconds later, there are not any display is shown on the display
panel and no voltage output is available from the UPS output.
4. Turn off the UPS with no utility power supplied (in Battery
mode)
1) To power off the UPS by pressing the OFF button continuously
for more than 1 second, and the buzzer will beep once.
2) When being powered off, the UPS will turn into No Output
mode. Finally not any display is shown on the display panel
and no voltage is available from the UPS output.
Suggestions:
Please turn off the connected loads before turning
on the UPS and turn on the loads one by one after the UPS is
working in INV mode. Turn off all of the connected loads before
turning off the UPS.
5. Maintenance operation instructions
1. Before removing the maintenance panel should select bypass
ON in display refer to the setting instructions in section 11.
2. Remove the maintenance panel with screws and turn the
maintenance switch from
³
UPS
´
to
³
BPS
´
, then the power will
be supplied through the bypass circuit and you may operate
on the UPS without any interruption
3. After finishing the operation, turn back the maintenance switch
from
³
BPS
´
to
³
UPS
´
and screw the maintenance cover board
back again.
Summary of Contents for Green Point 6 20KVA
Page 28: ...IV319 Rev 00 Data 2010 06 22 Pag 28 di 118 Wiring diagram of 6K 10K 1 1 parallel system...
Page 29: ...IV319 Rev 00 Data 2010 06 22 Pag 29 di 118 Wiring diagram of 10K 3 1 parallel system...
Page 57: ...IV319 Rev 00 Data 2010 06 22 Pag 57 di 118 DB 9 Interface of AS400 communication protocol...
Page 61: ...IV319 Rev 00 Data 2010 06 22 Pag 61 di 118 Back View of 15K 20K 3 1...