O P E R A T I N G I N S T R U C T I O N S | T - E A S I C
®
8023072/1E22/2022-02-23| SICK AG
Subject to change without notice
4 7
7
COMMISSIONING
7.4.16
Display Mode (industrial version only)
In this submenu, you can specify the information shown on the display during operation.
The following parameters are available for selection:
Parameter
Function
Flow & Temperature
The flow rate is shown in the lower part of the
display and the temperature in the upper part.
Flow & Volume
The flow rate is shown in the lower part of the
display and the volume in the upper part.
Volume & Temperature (Volume and Tem-
perature)
The volume is shown in the lower part of the
display and the temperature in the upper part.
7.4.17
Display Rotation (industrial version only)
In this submenu, you can rotate the display by 180°.
7.4.18
Display Lock (industrial version only)
To prevent setting changes, the display of the industrial version can be locked (HMI
locked). When the display is locked, an unlock password must be entered before any
changes can be made.
The password to unlock the display and keys is
000387
.
7.4.19
Simulation
Even if there is no liquid in the measurement channel yet, you can simulate a flow or
temperature in this submenu to test the sensor configuration. You can also simulate an
error state (safe state simulation).
b
Set the desired value for the flow or temperature using the arrow keys (up/down).
The following parameters are available for selection:
−
Off
−
Flow Simulation 0%
−
Flow Simulation 25%
−
Flow Simulation 50%
−
Flow Simulation 75%
−
Flow Simulation 100%
−
Temp Simulation –25 °C
−
Temp Simulation 0 °C
−
Temp Simu25 °C
−
Temp Simu50 °C
−
Temp Simu75 °C
−
Temp Simu100 °C
−
Temp Simu125 °C
−
Temp Simu150 °C
−
Simulate Failure
When a simulated state is activated, the display cyclically shows the message
Info
Simulation is active
. When a simulated fault condition is activated, the display cyclically
shows the message
Failure Failure Simulation is active
and the status LEDs S1 and
S2 flash simultaneously.