O P E R A T I N G I N S T R U C T I O N S | T - E A S I C
®
8023072/1E22/2022-02-23 | SICK AG
Subject to change without notice
4 6
7
COMMISSIONING
7.4.11
Delay Time Q1
In this submenu, you can set the delay time for Q1 according to the mode selected
under
Delay Mode Q1
). This menu is not available if
Delay Mode Q1
is set to Off.
7.4.12
Delay Mode Q2
This parameter is used to define the delay mode for Q2. The following parameters are
available for selection:
Parameter
Function
Off
No delay when a Q2 status change occurs.
Ton Delay
When
Q2 Switchpoint 1
is reached,
the status of Q2 does not change until
Delay time Q2
(see
Toff Delay
When
Q2 Switchpoint 2
is reached,
the status of Q2 does not change until
Delay time Q2
(see
Ton&Toff Delay
When
Q2 Switchpoint 1
is reached, the status of Q2
does not change until
Delay time Q2
Q2 Switchpoint 2
has been reached.
The status of Q2 does not change until
Delay time Q2
(see
7.4.13
Delay Time Q2
In this submenu, you can set the delay time for Q2 according to the mode selected
under
Delay Mode Q2
). This menu is not available when
Delay Mode Q2 Off
is set.
7.4.14
Error Current Q2a
In this submenu, you can configure how the analog output behaves in the event of a
critical device error. You can select whether to output 3.5mA or 21.5mA as a signal in
the event of an error. This menu item is only available in the electrical version B of the
T-Easic
®
FTS.
7.4.15
Display Language (industrial version only)
In this submenu, you can configure the display language - English or Chinese.
NOTE
If you set the Chinese language by mistake, you can return to the English menu by
pressing and holding the right arrow key and left arrow key simultaneously for 5 sec-
onds.