COMMISSIONING
6. Use the right/down arrow keys to select the
Teach max?
parameter.
The message
run ...
is displayed during the teach-in cycle.
If the teach-in completed successfully, the message
Teach OK
is displayed. If an
error occurred during teach-in, the message
Teach not OK
is displayed and the
steps described above must be repeated.
7.
Reduce the flow rate to the minimum flow rate.
8. Use the arrow keys (up/down) to select the
Teach min?
parameter. (Parameter
is displayed only after the
Teach max?
step has been successfully performed.)
The message
run ...
is displayed during the teach-in cycle.
If the teach-in completed successfully, the message
Teach OK
is displayed. If an
error occurred during teach-in, the message
Teach not OK
is displayed and the
steps described above must be repeated.
Measurement Mode
<
>
Velocity
Velocity
Volume
Teach
Medium
<
>
relative (%)
absolut
flow and counter
relative (%)
Water
Oil A
Oil B
Teach
<
>
Teach max?
Unit Pipe Diameter
<
>
25 mm
Teach
<
>
Teach min?
Teach Select
<
>
Teach 1
Teach 2
Teach 3
Always available
Error
Configuration-
dependent
Fig. 18:
Menu structure for configuring the measurement mode
NOTE
For optimum measurement accuracy, make sure that the medium teach-in is only
performed when
the medium temperature of the system has reached the steady state.