20 User manual GC600-GC600
Mains
In this page it is possible to change the power supplied in the application of parallel with the
mains
BASE LOAD
and
IMPORT/EXPORT
Page
M.02 (MAINS/BARS)
displays the main electrical measurements of Mains/Bus. In this page are
the voltages, the frequency and the rotation direction of the mains/bars phases. The information
really displayed depend on the configuration.
Three-phase system with neutral connected to the controller:
The controller shows the
three phase-to-phase voltages, the frequency, the rotation direction and the neutral-battery
voltages. By keeping the
ACK/ENTER
button pressed, in place of phase-to-phase
voltages, the phase voltages are shown.
Three-phase system without neutral.
The controller shows the three phase-to-phase
voltages, the frequency and the rotation direction.
Single-phase system.
The controller displays the phase voltage, the frequency and the
neutral-battery voltage.
Page
M.03
(
GENERATOR
) displays the electrical magnitudes of the
GENERATOR
. In this page the
voltages, the frequency and the rotation direction of the mains/bars are displayed. The information
really displayed depend on the configuration.
Three-phase system with neutral connected to the controller.
The controller shows the
three phase-to-phase voltages, the frequency, the rotation direction and the neutral-battery
voltages. By keeping the
ACK/ENTER
button pressed, in place of phase-to-phase
voltages, the phase voltages are shown.
Three-phase system without neutral.
The controller shows the three phase-to-phase
voltages, the frequency and the rotation direction.
Single-phase system.
The controller displays the phase voltage, the frequency and the
neutral-battery voltage.
Page
M.04 (CURRENTS)
displays the phase currents of the
Generator
/
Load
, the negative sequence
current, the auxiliary current, the neutral current and the differential current.
Page
M.05 (POWERS)
displays the active powers (kWh), the power factors and types of load on single
and total phases (for single-phase systems, the information relative to phases 2 and 3 are replaced
by dashes).
Page
M.06 (POWERS)
shows the reactive powers (kvar), and the apparent powers (kVA) on single and
total phases (for single-phase systems, the information related to phases 2 and 3 are replaced by
dashes).
Page
M.07 (ENERGY METERS)
displays the
Load
/
Generator
partial energy counters (active and
reactive energy), total energy (active and reactive energy). Available only if the configuration of the
CT (Current Transformer) is set to
Generator.
Page
M.08 (ENERGY METERS)
displays the
Load
/
Mains
partial energy counters (active and reactive
energy), total energy (active and reactive energy). Available only if the configuration of the CT
(Current Transformer) is set to
User
Page
M.09 (AUXILIARY MEASURES)
displays the additional information on genset voltages and
currents, used for the protection of the 27Q mains parallel.
Page
M.10 (REGULATIONS)
displays genset and mains/bus voltages and frequency at the same time.
It displays the parameters used to monitor the parallel operation. This window allows you to change
the power supplied in the mains parallel applications in BASE LOAD and IMPORT/EXPORT
operation.